Method
For parallel or counterflow, ΔTlm = (ΔT1 − ΔT2) / ln(ΔT1 / ΔT2). The calculator then uses Q̇ = U × A × F × ΔTlm, where F is the correction factor. For true parallel or counterflow, F is 1.
Worked example
For counterflow water cooling from 120 °C to 80 °C against a stream heated from 20 °C to 60 °C, both terminal differences are 60 K. The LMTD is therefore 60 K. At U = 200 W/(m²·K), A = 10 m² and F = 1, the estimated rate is 120 kW, or 120 kWh over one constant hour.
Important limits
This tool does not determine U, calculate exchanger area, perform a heat balance from flow rates or choose a correction factor. Do not use this direct model for phase change, crossflow or multi-pass arrangements without the appropriate correction factor and thermal-design method.
Frequently asked questions
What equation does the LMTD calculator use?
It calculates LMTD = (ΔT1 − ΔT2) / ln(ΔT1 / ΔT2), then heat-transfer rate Q̇ = U × A × F × LMTD. F is the LMTD correction factor.
When should the LMTD correction factor be 1?
Use F = 1 for true parallel-flow or counterflow exchangers. Crossflow and multi-pass exchangers may need a validated correction factor from the applicable thermal-design method.
Does the energy result predict plant consumption?
No. It multiplies the calculated heat-transfer rate by the duration you enter, assuming all inputs remain constant. It does not model pump power, changing loads, control behavior or utility tariffs.
Related tools
Sensible Heat Rate Calculator · Thermal Resistance & U-value Calculator · Heat Transfer Calculators