ELECTRICAL CALCULATOR

Cable Size Calculator

Calculate the minimum required conductor cross-section from current, distance, phase type and allowable voltage drop; the result is also rounded up to the nearest standard cross-section.

System type
Conductor material

Cross-section result

Recommended standard cross-section: 4 mm²

Allowed drop: 12 V

Resistivity used: ρ = 0.0175 Ω·mm²/m

Substituted formula

A = k x I x L x ρ / ΔU A = √3 x 20 A x 50 m x 0.0175 Ω·mm²/m / 12 V A = 2.5259074277 mm²

SI equivalent: 0.000002525907

What is this cable size tool used for?

This tool calculates the minimum conductor cross-section that satisfies a chosen voltage-drop limit, based on line current, cable length, conductor material and allowable voltage-drop percentage.

It can be used as a first-pass cross-section estimate for panel feeder circuits, motor and drive connections and remote field-equipment feeds.

Formula used

  • General: A = k x I x L x ρ / ΔU
  • This is the voltage-drop formula (ΔU = k x I x L x ρ / A) solved for cross-section.

Variables and meaning

I
Line current.
L
One-way cable length.
ρ
Conductor resistivity (approximate values at 20°C: copper 0.0175, aluminum 0.028 Ω·mm²/m).
ΔU
Allowable voltage drop, computed from source voltage and the allowed percentage.
k
Return-conductor or three-phase factor depending on system type.
A
Calculated required minimum cross-section.

Standard cross-section table

The result is rounded up to the first value at or above the calculated minimum from these common commercial cross-sections (mm²):

  • 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300

Unit reference tables

Voltage units

Unit nameSymbolSI equivalentTypical use
Millivolt (mV)mV0.001 VSensors and low-level signals
Volt (V)V1 VBase SI voltage unit
Kilovolt (kV)kV1,000 VHigh-voltage transmission

Current units

Unit nameSymbolSI equivalentTypical use
Milliampere (mA)mA0.001 AElectronic circuit currents
Ampere (A)A1 ABase SI current unit
Kiloampere (kA)kA1,000 AIndustrial power systems

Length units

Unit nameSymbolSI equivalentTypical use
Millimeter (mm)mm0.001 mThin layers and small diameters
Centimeter (cm)cm0.01 mShort dimensions
Meter (m)m1 mBase SI length unit
Kilometer (km)km1,000 mVery large distances and long layers
Inch (in)in0.0254 mImperial/US thickness measurements
Foot (ft)ft0.3048 mImperial/US length measurements

Worked examples

400 V, 20 A, 50 m, 3% allowable drop, copper, three-phase

ΔU_allowed = 400 x 0.03 = 12 V. A = 1.732 x 20 x 50 x 0.0175 / 12 which gives about 2.53 mm². The nearest standard cross-section is 4 mm².

230 V, 16 A, 25 m, 3% allowable drop, copper, single-phase

ΔU_allowed = 230 x 0.03 = 6.9 V. A = 2 x 16 x 25 x 0.0175 / 6.9 which gives about 2.03 mm². The nearest standard cross-section is 2.5 mm².

Typical applications

  • Panel feeder circuits
  • Motor and drive connections
  • Remote field-equipment feeds
  • Quick cross-section estimates during project estimation

Assumptions and limitations

  • This calculation recommends a cross-section based on the voltage-drop limit only; current-carrying capacity (ampacity), installation method, grouping and ambient-temperature corrections are not included.
  • The recommended cross-section must be verified separately against ampacity tables in the applicable electrical code (e.g. IEC, national or local regulations).
  • The resistivity values used (copper 0.0175, aluminum 0.028 Ω·mm²/m) are approximate 20°C reference values.
  • If the calculated cross-section exceeds the 300 mm² standard table, the tool does not suggest a standard value; a custom cross-section or parallel conductors should be evaluated.